C-C Sleeve connector
SLEEVE CONNECTOR, FOR COPPER CONDUCTORS
Gallery
Family
C-C
SLEEVE CONNECTOR, FOR COPPER CONDUCTORS
Certifications & approvals
-
USDA
Description
The C-C series connectors are made from electrolytic copper profile of more than 99.9% purity. They are the ideal choice for shunts from overhead lines in bare and insulated conductors, shunts from underground lines and grounding installations.
Thanks to the annealing process, the connectors are easier to compress and more resistant to mechanical stress, making them usable with a wide range of conductor cross-sections.
Read all
Close
Common features in table.
Features
Details by type in expandable section below.
Minimum operating temperature
-50 °C
Maximum operating temperature
150 °C
Crimping geometry
oval
Conductor body material
Electrolitic copper with purity above 99.95%
Annealing
Yes
Customs code
85369010
C-C
| Technical information | Weight and dimensions | Logistic | Certifications | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| tipo | Type of branch circuit | Cross section range of the through cable [mm²] | Cross section range of the through cable (alternative) [mm²] | Cross section range of the branch cable [mm²] | Cross section range of the branch cable (alternative) [mm²] | C [mm] | L [mm] | B [mm] | Unit in minimal packaging [pce] | Unit in standard packaging [pce] | ROHS compliant |
| C6-C6 | tap connection; joint connection | 2.5 - 6 | 1.5 - 6 | 9 | 9.8 | 6.4 | 100 | 1500 | Yes | ||
| C10-C10 | tap connection; joint connection | 10 | 1.5 - 10 | 12 | 12.6 | 8.4 | 100 | 500 | Yes | ||
| C16-C16 | tap connection; joint connection | 16 | 1.5 - 16 | 17 | 19.4 | 12 | 100 | 400 | Yes | ||
| C25-C10 | tap connection; joint connection | 16 - 25 | 1.5 - 10 | 17 | 19.8 | 13 | 50 | 400 | Yes | ||
| C25-C25 | tap connection; joint connection | 25 | 16 - 25 | 17 | 21.4 | 13 | 50 | 300 | Yes | ||
| C35-C16 | tap connection; joint connection; joining two running conductors | 35 - 40 | 1.5 - 16 | 21 | 24.6 | 15.4 | 25 | 200 | Yes | ||
| C35-C35 | tap connection; joint connection; joining two running conductors | 50; 35 - 40 | 10 - 25; 25 - 40 | 21 | 26.6 | 15.6 | 25 | 200 | Yes | ||
| C70-C25N | tap connection; joint connection | 63 - 70 | 1.5 - 25 | 21 | 26.4 | 17.5 | 25 | 200 | Yes | ||
| C50-C25 | tap connection; joint connection | 50 | 4 - 25 | 25 | 32.9 | 21 | 25 | 75 | Yes | ||
| C50-C50 | tap connection; joint connection | 50 | 35 - 50 | 26 | 33 | 21 | 25 | 75 | Yes | ||
| C70-C35 | tap connection; joint connection | 50 - 70 | 4 - 40 | 28 | 33 | 21 | 25 | 75 | Yes | ||
| C70-C70 | tap connection; joint connection; joining two running conductors | 50 - 70 | 35 - 70 | 28 | 34 | 21 | 25 | 75 | Yes | ||
| C95-C35 | tap connection; joint connection | 95 - 100 | 4 - 40 | 29 | 40.6 | 26 | 25 | 50 | Yes | ||
| C95-C70 | tap connection; joint connection; joining two running conductors | 95 - 100 | 40 - 70 | 29 | 41 | 26 | 25 | 50 | Yes | ||
| C95-C95 | tap connection; joint connection | 95 - 100 | 63 - 100 | 29 | 41 | 26 | 25 | 50 | Yes | ||
| C120-C120 | tap connection; joint connection | 110 - 125 | 25 - 125 | 30 | 45 | 28 | 15 | 30 | Yes | ||
| C150-C120 | tap connection; joint connection; joining two running conductors | 125; 150 - 160 | 125; 25 - 125 | 31 | 45 | 28 | 15 | 30 | Yes | ||
| C150-C150 | tap connection; joint connection; joining two running conductors | 125 | 150 | 125 | 63 - 150 | 30 | 45 | 28 | 15 | 30 | Yes |
| C185-C95 | tap connection; joint connection; joining two running conductors | 185 | 16 - 100 | 31 | 45 | 28 | 15 | 30 | Yes | ||
| C185-C185 | tap connection; joint connection | 120 - 185 | 120 - 185 | 22.6 | 68 | 34 | 15 | 30 | Yes | ||
| C240-C120 | tap connection; joint connection | 150 - 240 | 95 - 120 | 22.6 | 68 | 34 | 15 | 30 | Yes | ||
C6-C6
Type of branch circuit
tap connection; joint connection
Cross section range of the through cable [mm²]
2.5 - 6
Cross section range of the through cable (alternative) [mm²]
–
Cross section range of the branch cable [mm²]
1.5 - 6
Cross section range of the branch cable (alternative) [mm²]
–
C [mm]
9
L [mm]
9.8
B [mm]
6.4
Unit in minimal packaging [pce]
100
Unit in standard packaging [pce]
1500
ROHS compliant
Yes
C10-C10
Type of branch circuit
tap connection; joint connection
Cross section range of the through cable [mm²]
10
Cross section range of the through cable (alternative) [mm²]
–
Cross section range of the branch cable [mm²]
1.5 - 10
Cross section range of the branch cable (alternative) [mm²]
–
C [mm]
12
L [mm]
12.6
B [mm]
8.4
Unit in minimal packaging [pce]
100
Unit in standard packaging [pce]
500
ROHS compliant
Yes
C16-C16
Type of branch circuit
tap connection; joint connection
Cross section range of the through cable [mm²]
16
Cross section range of the through cable (alternative) [mm²]
–
Cross section range of the branch cable [mm²]
1.5 - 16
Cross section range of the branch cable (alternative) [mm²]
–
C [mm]
17
L [mm]
19.4
B [mm]
12
Unit in minimal packaging [pce]
100
Unit in standard packaging [pce]
400
ROHS compliant
Yes
C25-C10
Type of branch circuit
tap connection; joint connection
Cross section range of the through cable [mm²]
16 - 25
Cross section range of the through cable (alternative) [mm²]
–
Cross section range of the branch cable [mm²]
1.5 - 10
Cross section range of the branch cable (alternative) [mm²]
–
C [mm]
17
L [mm]
19.8
B [mm]
13
Unit in minimal packaging [pce]
50
Unit in standard packaging [pce]
400
ROHS compliant
Yes
C25-C25
Type of branch circuit
tap connection; joint connection
Cross section range of the through cable [mm²]
25
Cross section range of the through cable (alternative) [mm²]
–
Cross section range of the branch cable [mm²]
16 - 25
Cross section range of the branch cable (alternative) [mm²]
–
C [mm]
17
L [mm]
21.4
B [mm]
13
Unit in minimal packaging [pce]
50
Unit in standard packaging [pce]
300
ROHS compliant
Yes
C35-C16
Type of branch circuit
tap connection; joint connection; joining two running conductors
Cross section range of the through cable [mm²]
35 - 40
Cross section range of the through cable (alternative) [mm²]
–
Cross section range of the branch cable [mm²]
1.5 - 16
Cross section range of the branch cable (alternative) [mm²]
–
C [mm]
21
L [mm]
24.6
B [mm]
15.4
Unit in minimal packaging [pce]
25
Unit in standard packaging [pce]
200
ROHS compliant
Yes
C35-C35
Type of branch circuit
tap connection; joint connection; joining two running conductors
Cross section range of the through cable [mm²]
50; 35 - 40
Cross section range of the through cable (alternative) [mm²]
–
Cross section range of the branch cable [mm²]
10 - 25; 25 - 40
Cross section range of the branch cable (alternative) [mm²]
–
C [mm]
21
L [mm]
26.6
B [mm]
15.6
Unit in minimal packaging [pce]
25
Unit in standard packaging [pce]
200
ROHS compliant
Yes
C70-C25N
Type of branch circuit
tap connection; joint connection
Cross section range of the through cable [mm²]
63 - 70
Cross section range of the through cable (alternative) [mm²]
–
Cross section range of the branch cable [mm²]
1.5 - 25
Cross section range of the branch cable (alternative) [mm²]
–
C [mm]
21
L [mm]
26.4
B [mm]
17.5
Unit in minimal packaging [pce]
25
Unit in standard packaging [pce]
200
ROHS compliant
Yes
C50-C25
Type of branch circuit
tap connection; joint connection
Cross section range of the through cable [mm²]
50
Cross section range of the through cable (alternative) [mm²]
–
Cross section range of the branch cable [mm²]
4 - 25
Cross section range of the branch cable (alternative) [mm²]
–
C [mm]
25
L [mm]
32.9
B [mm]
21
Unit in minimal packaging [pce]
25
Unit in standard packaging [pce]
75
ROHS compliant
Yes
C50-C50
Type of branch circuit
tap connection; joint connection
Cross section range of the through cable [mm²]
50
Cross section range of the through cable (alternative) [mm²]
–
Cross section range of the branch cable [mm²]
35 - 50
Cross section range of the branch cable (alternative) [mm²]
–
C [mm]
26
L [mm]
33
B [mm]
21
Unit in minimal packaging [pce]
25
Unit in standard packaging [pce]
75
ROHS compliant
Yes
C70-C35
Type of branch circuit
tap connection; joint connection
Cross section range of the through cable [mm²]
50 - 70
Cross section range of the through cable (alternative) [mm²]
–
Cross section range of the branch cable [mm²]
4 - 40
Cross section range of the branch cable (alternative) [mm²]
–
C [mm]
28
L [mm]
33
B [mm]
21
Unit in minimal packaging [pce]
25
Unit in standard packaging [pce]
75
ROHS compliant
Yes
C70-C70
Type of branch circuit
tap connection; joint connection; joining two running conductors
Cross section range of the through cable [mm²]
50 - 70
Cross section range of the through cable (alternative) [mm²]
–
Cross section range of the branch cable [mm²]
35 - 70
Cross section range of the branch cable (alternative) [mm²]
–
C [mm]
28
L [mm]
34
B [mm]
21
Unit in minimal packaging [pce]
25
Unit in standard packaging [pce]
75
ROHS compliant
Yes
C95-C35
Type of branch circuit
tap connection; joint connection
Cross section range of the through cable [mm²]
95 - 100
Cross section range of the through cable (alternative) [mm²]
–
Cross section range of the branch cable [mm²]
4 - 40
Cross section range of the branch cable (alternative) [mm²]
–
C [mm]
29
L [mm]
40.6
B [mm]
26
Unit in minimal packaging [pce]
25
Unit in standard packaging [pce]
50
ROHS compliant
Yes
C95-C70
Type of branch circuit
tap connection; joint connection; joining two running conductors
Cross section range of the through cable [mm²]
95 - 100
Cross section range of the through cable (alternative) [mm²]
–
Cross section range of the branch cable [mm²]
40 - 70
Cross section range of the branch cable (alternative) [mm²]
–
C [mm]
29
L [mm]
41
B [mm]
26
Unit in minimal packaging [pce]
25
Unit in standard packaging [pce]
50
ROHS compliant
Yes
C95-C95
Type of branch circuit
tap connection; joint connection
Cross section range of the through cable [mm²]
95 - 100
Cross section range of the through cable (alternative) [mm²]
–
Cross section range of the branch cable [mm²]
63 - 100
Cross section range of the branch cable (alternative) [mm²]
–
C [mm]
29
L [mm]
41
B [mm]
26
Unit in minimal packaging [pce]
25
Unit in standard packaging [pce]
50
ROHS compliant
Yes
C120-C120
Type of branch circuit
tap connection; joint connection
Cross section range of the through cable [mm²]
110 - 125
Cross section range of the through cable (alternative) [mm²]
–
Cross section range of the branch cable [mm²]
25 - 125
Cross section range of the branch cable (alternative) [mm²]
–
C [mm]
30
L [mm]
45
B [mm]
28
Unit in minimal packaging [pce]
15
Unit in standard packaging [pce]
30
ROHS compliant
Yes
C150-C120
Type of branch circuit
tap connection; joint connection; joining two running conductors
Cross section range of the through cable [mm²]
125; 150 - 160
Cross section range of the through cable (alternative) [mm²]
–
Cross section range of the branch cable [mm²]
125; 25 - 125
Cross section range of the branch cable (alternative) [mm²]
–
C [mm]
31
L [mm]
45
B [mm]
28
Unit in minimal packaging [pce]
15
Unit in standard packaging [pce]
30
ROHS compliant
Yes
C150-C150
Type of branch circuit
tap connection; joint connection; joining two running conductors
Cross section range of the through cable [mm²]
125
Cross section range of the through cable (alternative) [mm²]
150
Cross section range of the branch cable [mm²]
125
Cross section range of the branch cable (alternative) [mm²]
63 - 150
C [mm]
30
L [mm]
45
B [mm]
28
Unit in minimal packaging [pce]
15
Unit in standard packaging [pce]
30
ROHS compliant
Yes
C185-C95
Type of branch circuit
tap connection; joint connection; joining two running conductors
Cross section range of the through cable [mm²]
185
Cross section range of the through cable (alternative) [mm²]
–
Cross section range of the branch cable [mm²]
16 - 100
Cross section range of the branch cable (alternative) [mm²]
–
C [mm]
31
L [mm]
45
B [mm]
28
Unit in minimal packaging [pce]
15
Unit in standard packaging [pce]
30
ROHS compliant
Yes
C185-C185
Type of branch circuit
tap connection; joint connection
Cross section range of the through cable [mm²]
120 - 185
Cross section range of the through cable (alternative) [mm²]
–
Cross section range of the branch cable [mm²]
120 - 185
Cross section range of the branch cable (alternative) [mm²]
–
C [mm]
22.6
L [mm]
68
B [mm]
34
Unit in minimal packaging [pce]
15
Unit in standard packaging [pce]
30
ROHS compliant
Yes
C240-C120
Type of branch circuit
tap connection; joint connection
Cross section range of the through cable [mm²]
150 - 240
Cross section range of the through cable (alternative) [mm²]
–
Cross section range of the branch cable [mm²]
95 - 120
Cross section range of the branch cable (alternative) [mm²]
–
C [mm]
22.6
L [mm]
68
B [mm]
34
Unit in minimal packaging [pce]
15
Unit in standard packaging [pce]
30
ROHS compliant
Yes
Follow us
Subscribe to CEMBRE newsletter and stay tuned
Thank you, your request has been send successfully
You'll be contact soon by our commercial staff
Print label service
Fill in the form and follow the instructions to request the label print service
Thank you, your request has been send successfully
You'll be contact soon by our commercial staff