L-M THROUGH CONNECTOR

THROUGH CONNECTOR, FOR COPPER CONDUCTORS
Documentation
Certifications & approvals
  • UL (cULus)
    UL (cULus)
Description
L-M range of connectors are designed for jointing low voltage conductors. Made of electrolytic Copper tube with a purity greater than 99.9%, having the same dimension as A-M series lugs: L-M connectors are annealed and electrolytically Tin plated. They feature an internal taper at both ends to ease the introduction of the conductor and a central stop to ensure correct positioning.
Read all Close

Common features in table.

Features
Details by type in expandable section below.
  • Technical information
  • Material composition and treatments
  • Classification and data ordering
  • Certifications
Minimum operating temperature
-50   °C
Maximum operating temperature
150   °C
Central stop
Yes
Easy insertion input
Yes
Surface treatment
tin plating
Crimping geometry
hexagonal; indent
Conductor body material
Rame elettrolitico con purezza superiore al 99,95%
Annealing
Yes
Customs code
85369010
ROHS compliant
Yes

drwr-dim
L-M
Technical information Weight and dimensions Logistic Certifications
tipo Type of connector Range of cable cross section (flexible) [mm²] Range of cable cross section (low stranded) [mm²] L [mm] A [mm] Ø [mm] Cable stripping length [mm] Ø1 [mm] Unit in minimal packaging [pce] Unit in standard packaging [pce] Reference standard UL standard
L03-M butt through connector 0.25 - 1.5 0.25 - 1.5 15 7.5 1.8 9 3.3 100 5000
L06-M butt through connector 1.5 - 2.5 1.5 - 2.5 15 7.5 2.42 9 4 100 4000
L1-M butt through connector 4 - 6 4 22 11 3.6 13 5.25 100 2000 UL 486A-486B UL486A-486B
L2-M butt through connector 10 10 25 12.5 4.6 14 6.8 100 1000 UL 486A-486B UL486A-486B
L3-M butt through connector 16 16 27 13.5 5.8 15 7.9 100 500 UL 486A-486B UL486A-486B
L5-M butt through connector 25 25 29 14.5 7 16 9.3 100 500 UL 486A-486B UL486A-486B
L7-M butt through connector 25 - 35 35 33 16.5 8.9 19 11.7 100 400 UL 486A-486B UL486A-486B
L10-M butt through connector 35 - 50 50 37 18.5 10 21 13 50 200 UL 486A-486B UL486A-486B
L14-M butt through connector 50 - 70 70 39 19.5 11.3 22 14.6 50 200 UL 486A-486B UL486A-486B
L19-M butt through connector 70 - 95 95 43 21.5 13.5 24 17.5 25 100 UL 486A-486B UL486A-486B
L24-M butt through connector 95 - 120 120 47 23.5 15.2 26 19.6 25 75 UL 486A-486B UL486A-486B
L30-M butt through connector 120 - 150 150 58 29 16.7 32 21.5 25 50 UL 486A-486B UL486A-486B
L37-M butt through connector 150 - 185 185 64 32 19.2 36 24.4 15 30 UL 486A-486B UL486A-486B
L48-M butt through connector 185 - 240 240 75 37.5 21.1 42 27.2 10 20 UL 486A-486B UL486A-486B
L60-M butt through connector 240 - 300 300 90 45 23.7 50 30.6 10 20 UL 486A-486B UL486A-486B
L80-M butt through connector 300 - 400 300 94 47 27 52 35 5 15 UL 486A-486B UL486A-486B
L100-M butt through connector 400 - 500 400 98 49 30.3 54 39.5 1 12 UL486A-486B
L120-M butt through connector 500 - 630 500 105 52.5 33.4 58 42.6 1 10
L160-M parallel through connector 600 800 112 56 38 62 50 1 6
L200-M parallel through connector 800 800 120 60 44 66 56 1 6

Follow us

Subscribe to CEMBRE newsletter and stay tuned

Print label service

Fill in the form and follow the instructions to request the label print service

1. User data

2. Company data

3. Print type

4. Label specs

Orientation

Label size

A x B mm

5. Graphic specs

Graphic size

H x W mm

Graphic position

X x Y mm

6. Request data